| Features: |
AC input range selected by switch
Approvals:UL/CUL/TUV/CB/CE
UL508 listed approved
Free air cooling convection Installed on DIN Rail TS35 / 7.5 or 15
LED indicator for power on
100% full load burn-in test
3 years warranty |
|
| Specifications: |
| Parameter |
Description/SPEC.: |
| Input Voltage |
88 ~ 132 VAC ; 176 ~ 264 VDC |
| Inrush Current |
cold start, 30 A / 115 V, 60 A / 230 V |
| DC adjust range |
12V: 12~14V, 24V: 24 ~ 28V, 48V: 48 ~ 53V |
| O.L.P. |
105% ~ 150% constant current, Auto recovery |
| O.V.P. |
120% ~ 140% rated output voltage |
| Setup,rise, hold up time |
500ms, 70ms, 30ms at full load and 230 VAC |
| Withstand Voltage |
I/P-O/P: 3K VAC, I/P-FG: 1.5K VAC, 1min. |
| Working temp. |
-10 ¢J ~ 60 ¢J (refer to output derating curve) |
| Safety standard |
UL 508, TUV EN 60950-1, UL60950-1 |
| EMC standard |
EN55022, EN61000-3-2,3, |
| |
EN61000-4-2,3,4,5,6,8,11, ENV50204, EN61000-6-2 |
| Connection |
I/P: 3 poles , O/P: 4 poles screw DIN terminal |
| Weight/packing |
0.79 kg; 20 pcs / 16.5 kgs / 1.1 CUFT |
|
|
| No. |
Model |
Input |
Output |
Iomin |
Iomax |
Load Reg. |
Power |
| 1. |
DR-120-12 |
88~132VAC;176~264 VAC |
+ 12.00VDC |
.00A |
10.00A |
±2.00% |
120.000(w) |
| 2. |
DR-120-24 |
88~132VAC;176~264 VAC |
+ 24.00VDC |
.00A |
5.00A |
±1.00% |
120.000(w) |
| 3. |
DR-120-48 |
88~132VAC;176~264 VAC |
+ 48.00VDC |
.00A |
2.50A |
±1.00% |
120.000(w) |
| Other Informations: |