| Features: |
Universal AC input/Full Range
Approvals:UL/CUL/TUV/CB/CE
UL508 listed approved
Free air convection Installed on DIN Rail TS35/7.5 or 15
LED indication for power on
100% full load burn-in test
3 years warranty
|
|
| Specifications: |
| Parameter |
Description/SPEC.: |
| Input Voltage |
85 ~ 264 VAC ; 120 ~ 370 VDC |
| Inrush Current |
cold start, 30A / 115 V, 60A / 230 V |
| DC adjust range |
12V: 12 ~ 14V, 24V: 24 ~ 28V, 48V: 48 ~ 53V |
| O.L.P. |
115% ~ 150% constant current, Auto recovery |
| O.V.P. |
121% ~ 142% rated output voltage |
| Setup,rise, hold up time |
1000ms, 60ms, 50ms @ 230 VAC |
| Withstand Voltage |
I/P-O/P:3KV, I/P-FG: 1.5KV, 1min. |
| Working temp. |
-10¢J ~ 60 ¢J (refer to output derating curve) |
| Safety standard |
UL 508, TUV EN 60950-1 |
| EMC standard |
EN55022 class B, EN61000-3-2,3, |
| |
EN61000-4-2,3,4,5,6,8,11, ENV50204, EN61000-6-2 |
| Connection |
I/P: 3 Poles, O/P: 4 poles screw terminal DIN terminal |
| Weight/packing |
0.6kg ; 20 pcs / 13.0 kgs / 1.1 CUFT |
|
|
| No. |
Model |
Input |
Output |
Iomin |
Iomax |
Load Reg. |
Power |
| 1. |
DR-75-12 |
85~264VAC;120~370 VDC |
+ 12.00VDC |
.00A |
6.30A |
±2.00% |
75.000(w) |
| 2. |
DR-75-24 |
85~264VAC;120~370 VDC |
+ 24.00VDC |
.00A |
3.20A |
±1.00% |
75.000(w) |
| 3. |
DR-75-48 |
85~264VAC;120~370 VDC |
+ 48.00VDC |
.00A |
1.60A |
±1.00% |
75.000(w) |
| Other Informations: |
| MECHANISM |
 |
|
|