| Features: |
Input 340~550VAC, 3-phase 4 wires
Protections: Short circuit / OLP / OVP/ OTP
Installed on Din rail TS35/7.5 or 15 100% full load burn-in test
Approvals: UL / CUL / TUV / CB / CE
EN61000-6-2 industrial immunity level
3 years warranty |
|
| Specifications: |
| Parameter |
Description/SPEC.: |
| AC Input Voltage Range |
340 ~ 550 VAC; 3 - Phase 4 wires |
| AC Inrush Current |
cold start, 50A |
| DC Adjustment Range |
24 ~ 28 V for 24 V model, 48 ~ 55 V for 48 V model |
| Over load Protection |
105% ~ 150% constant current, auto-recovery |
| Over voltage protection |
30 ~ 36 V for 24 V model, 59 ~ 66 V for 48 V shut off |
| Withstand VoltageĦ@ |
I/P-O/P: 3K VAC, I/P-FG: 1.5K VAC, 1 minute |
| Working Temperature |
-20 ˘J ~ 70 ˘J (refer to output derating curve) |
| Safety standard |
UL508, UL60950-1, TUV EN60950-1 |
| EMC Standards |
EN55022 class B, EN61000-3-2,3, EN61204-3, EN61000-4-2,3,4,5,6,8,11, EN50204, EN61000-6-2 |
| Connection |
I/P: 4 poles, O/P: 4 poles screw DIN terminal |
| Weight/packing |
1.3kgs; 12 pcs / 16.6 kgs / 1.34 CUFT |
| Dimension |
125.5 X 125.2 X 100 mm |
|
|
| No. |
Model |
Input |
Output |
Iomin |
Iomax |
Load Reg. |
Power |
| 1. |
DRT-240-24 |
340~550 VAC |
+ 24.00VDC |
.00A |
10.00A |
±5.00% |
240.000(w) |
| 2. |
DRT-240-48 |
340~550 VAC |
+ 48.00VDC |
.00A |
5.00A |
±5.00% |
240.000(w) |
| Other Informations: |
|
 |
|
|